LCM IIÀÇ Àû¿ë
The
LCM has been used since 1989 to determine short term as well
as long-term measurements on arresters from 66kV to 765kV
networks, and is today delivered
to power companies and utilities in about 50 different countries.
Performing
Field Measurements
LCM can only be used for arresters on insulated base and with
a separate earth lead.
Arrester
ID is downloaded from PC software to LCM II instrument prior
to performing inspection of surge arresters. LCM II can store
1000 arrester ID¡¯s.
On
location choose correct arrester ID and perform measurement.
LCM II can store 1000 measurements performed in the field.
After
completion of field measurements stored data are transferred
from LCM II instrument to PC software. You are now ready to
perform analysis and plan your next inspection.

General overview of LCM II condition monitoring system.
|
LCM
II - The Technique
Well-proven and acknowledged monitoring technique using third-order
harmonic analysis with compensation.
Rated
according IEC 60099-5 as the best field monitoring technique
for Metal Oxide Surge Arresters (MOSA).
LCM
II records operating voltage and temperature during field
measurements.
The
LCM II measurements are automatically normalized to standard
ambient temperature (+20¡ÆC) and 0.7x rated arrester voltage
based on recorded temperature and operating voltage during
field measurement. Measurements performed under different
conditions can thereby easily be compared.
|