PCR
( Polarization Cell Replacement)
|
| |
|
|
|
The PCR is a solid-state device designed to simultaneously provide
DC decoupling and AC continuity/grounding when used with cathodically
protected structures, such as pipelines, tanks, grounding systems,
and cable casings.
The PCR is an ideal replacement for electrochemical polarization
cells.
In a compact, solid-state package, the PCR has high AC fault
current and lightning surge current ratings.
With a higher blocking voltage than polarization cells, the
PCR eliminates the need for placing devices in series.
It also outperforms any metal oxide varistor or gapped arrester,
clamping lightning-caused over-voltages to the lowest possible
levels. |
|
Typical
Applications
- Protection of Insulated
Joints
- DC decoupling from Power
Utility Grounding Systems
- AC Voltage Mitigation on
Pipeline Systems
- AC Grounding/DC decoupling
of Electrical Equipment from Station Ground
Features
& Characteristics
- Higher Blocking Voltage
than Polarization Cells
- No Maintenance Needed
- Solid-state, Fail-safe
Design
- No Hazardous Electrolytes
- UL and CSA
Listed for Grounding Electrical Equipment
- Unlimited Number of Operations
- Compact Package
Ratings
- 60Hz
Ratings
| DC
Voltage Blocking: |
-3/+1V
(standard)
-4/+1V (optional)
-2/+2V (optional symmetrical unit) |
| Lightning
Surge Current: |
100,000A
crest (8 x 20 ¥ìs waveform) |
| Steady-state
AC Current (Amperes - rms): |
45A
(standard)
80A (optional) |
AC Fault Current (Amperes - rms):
|
Catalog
Code
|
1
cycle
|
3
cycle
|
10
cycle
|
30
cycle
|
|
PCR-3.7KA
|
6,500
|
5,000
|
4,200
|
3,700
|
|
PCR-10KA
|
20,000
|
15,000
|
12,000
|
10,000
|
|
PCR-15KA
|
35,000
|
27,000
|
21,000
|
15,000
|
|
|
|
|
|
|
Options
- Compact Connectors (CC): replaces standard
terminals
- Insulated Joint Mounting Kit
- 50Hz
Ratings
| DC
Voltage Blocking: |
-3/+1V
(standard)
-4/+1V (optional)
-2/+2V (optional symmetrical unit) |
| Lightning
Surge Current: |
100,000A
crest (8 x 20 ¥ìs waveform) |
| Steady-state
AC Current (Amperes - rms): |
45A
(standard)
80A (optional) |
AC Fault Current (Amperes - rms):
|
Catalog
Code
|
1
cycle
|
3
cycle
|
10
cycle
|
30
cycle
|
|
PCR-3.5KA
|
6,100
|
4,700
|
3,900
|
3,500
|
|
PCR-9KA
|
19,000
|
14,000
|
11,000
|
9,000
|
|
PCR-14KA
|
33,000
|
25,000
|
20,000
|
14,000
|
Options
- Compact Connectors (CC): replaces standard
terminals
- Insulated Joint Mounting Kit
 |
|
|
|