The PCR is a solid-state device designed to simultaneously provide DC decoupling and AC continuity/grounding when used with cathodically protected structures, such as pipelines, tanks, grounding systems, and cable casings.

The PCR is an ideal replacement for electrochemical polarization cells.
In a compact, solid-state package, the PCR has high AC fault current and lightning surge current ratings.
With a higher blocking voltage than polarization cells, the PCR eliminates the need for placing devices in series.
It also outperforms any metal oxide varistor or gapped arrester, clamping lightning-caused over-voltages to the lowest possible levels.



Typical Applications

  • Protection of Insulated Joints
  • DC decoupling from Power Utility Grounding Systems
  • AC Voltage Mitigation on Pipeline Systems
  • AC Grounding/DC decoupling of Electrical Equipment from Station Ground



Features & Characteristics

  • Higher Blocking Voltage than Polarization Cells
  • No Maintenance Needed
  • Solid-state, Fail-safe Design
  • No Hazardous Electrolytes
  • UL and CSA Listed for Grounding Electrical Equipment
  • Unlimited Number of Operations
  • Compact Package

Ratings

  • 60Hz Ratings

    DC Voltage Blocking: -3/+1V (standard)
    -4/+1V (optional)
    -2/+2V (optional symmetrical unit)
    Lightning Surge Current: 100,000A crest (8 x 20 ¥ìs waveform)
    Steady-state AC Current (Amperes - rms): 45A (standard)
    80A (optional)

    AC Fault Current (Amperes - rms):

    Catalog Code
    1 cycle
    3 cycle
    10 cycle
    30 cycle
    PCR-3.7KA
    6,500
    5,000
    4,200
    3,700
    PCR-10KA
    20,000
    15,000
    12,000
    10,000
    PCR-15KA
    35,000
    27,000
    21,000
    15,000

    Options


    - Compact Connectors (CC): replaces standard terminals
    - Insulated Joint Mounting Kit



  • 50Hz Ratings

    DC Voltage Blocking: -3/+1V (standard)
    -4/+1V (optional)
    -2/+2V (optional symmetrical unit)
    Lightning Surge Current: 100,000A crest (8 x 20 ¥ìs waveform)
    Steady-state AC Current (Amperes - rms): 45A (standard)
    80A (optional)


    AC Fault Current (Amperes - rms):

    Catalog Code
    1 cycle
    3 cycle
    10 cycle
    30 cycle
    PCR-3.5KA
    6,100
    4,700
    3,900
    3,500
    PCR-9KA
    19,000
    14,000
    11,000
    9,000
    PCR-14KA
    33,000
    25,000
    20,000
    14,000