The
Arbiter Systems¢ç, Inc. Model 936A Reference Current Transformer
provides laboratory grade accuracy in a small, portable, ruggedized
case, making it ideal for field use. Multiple ratios of 1200:5,
1000:5, 800:5, 600:5 are selectable via a front panel switch.
The guaranteed accuracy over the full input range and operating
conditions is 0.02% ratio and 0.01¡Æ phase (traceable to NIST),
ideal for calibrating other current transformers.
The
Model 936A uses an active transformer to achieve the high
accuracy needed for a primary reference. This design incorporates
a dual core toroid with an amplifier aided second stage. The
active circuitry reduces the sense transformer core flux to
zero and produces an accurate output current independent of
burden. The Model 936A was designed primarily for use with
the Model 935A Current Source and the Model 931A Power System
Analyzer to calibrate current transformers used with the Model
1133A Power Sentinel. The Model 936A's multiple ratio selections
allow other current transformers to be tested and calibrated
across their entire operating range.
936A Specifications
I/O Configuration
Input
Input Range : 1 to 1200 Arms
Current Ratios : 1200:5, 1000:5, 800:5, 600:5
Output
Current : 5 Arms maximum
Voltage : 8.5 Vrms maximum
Power
Requirements
External Power
Range : 85 to 264 Vac, 47 to 440 Hz, 15 VA maximum or 110
to 250 Vdc, 15 W maximum
Safety : Designed to meet UL, CSA, VDE Standard
Inlet : IEC-320 with fuse and mating cordset. Specify P01-P10.
General
Physical
Case Size : 205 x 305 x 225 mm (8 x 12 x 8.75 in.)
Weight : 5.8 kg (12.8 lbs) maximum
Sense Transformer : 51 mm (2.0 in.) ID Nominal
Environmental
Temperature Operating : 0¡Æ to +40¡Æ C
Non-operating : -40¡Æ to +85¡Æ C
Humidity : Non-condensing
|